KL2408 Bus Terminal Technical Data:
Technical data |
KL2408 |
Connection technology |
1-wire |
Number of outputs |
8 |
Nominal voltage |
24 V DC (-15 %/+20 %) |
Load type |
ohmic, inductive, lamp load |
Max. output current |
0.5 A (short-circuit proof) per channel |
Short-circuit current |
< 2 A |
Breaking energy |
< 150 mJ/channel |
Reverse voltage protection |
yes |
Electrical isolation |
500 V (K-bus/field potential) |
Current consumption power contacts |
typ. 60 mA + load |
Current consumption K-bus |
typ. 18 mA |
Bit width in the process image |
8 outputs |
Configuration |
no address or configuration setting |
Weight |
approx. 70 g |
Operating/storage temperature |
-25…+60 °C/-40…+85 °C |
Relative humidity |
95 %, no condensation |
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. |
IP20/variable |
Pluggable wiring |
for all KSxxxx Bus Terminals |
Approvals/markings |
CE, UL, ATEX, DNV GL, IECEx, cFMus |
Ex marking |
ATEX: |
II 3 G Ex nA IIC T4 Gc |
|
IECEx: |
|
Ex nA IIC T4 Gc |
|
Ex tc IIIC T135 °C Dc |
|
cFMus: |
|
Class I, Division 2, Groups A, B, C, D |
|